Building Standard Library

national standards of People's Republic of China

Building fire extinguisher configuration design code

Code for design of extinguisher
distribution in buildings

GB 50140-2005

Compiling department: Ministry of Public Security of the People's Republic of China Approval department: Ministry of Construction of the People's Republic of China Date of implementation: October 1, 2005

Announcement of the Ministry of Construction of the People's Republic of China

No. 355

Announcement of the Ministry of Construction on Issuing the National Standard "Code for Design and Design of Fire Extinguishers in Buildings"

The "Code for the Design of Fire Extinguisher Configuration" is now approved as the national standard, numbered GB 50140-2005, and will be implemented from October 1, 2005. Among them, sections 4.1.3, 4.2.1, 4.2.2, 4.2.3, 4.2.4, 4.2.5, 5.1.1, 5.1.5 , 5.2.1, 5.2.2, 6.1.1, 6.2.1, 6.2.2, 7.1.2, 7.1.3 are mandatory and must be strict carried out. The original GBJ 140-90 of the "Code for Design and Design of Building Fire Extinguishers" was abolished at the same time.
This specification is published by the China Planning Publishing House organized by the Standard Quota Research Institute of the Ministry of Construction.

Ministry of Construction of the People's Republic of China July 15, 2005

Foreword

This code is based on the requirements of the Ministry of Construction Jianbiao [2001] No. 087 "Notice on Printing and Distributing the" 2000-2001 Project National Construction Standard Development and Revision Plan "Notice", and the Ministry of Public Security Shanghai Fire Research Institute It was prepared on the basis of a comprehensive revision of the 1997 edition of the original national standard "Code for Design and Design of Building Fire Extinguishers", GBJ 140-90, in conjunction with relevant units.
In the process of compiling this code, in-depth investigations and studies are conducted with reference to similar domestic and foreign codes, and it has repeatedly communicated with scientific research, design, construction, and use units. Based on extensive consultation, it has actively absorbed domestic and foreign building fire extinguisher configurations The mature experience of engineering design and application, combined with the actual situation of China's current stage of engineering, after repeated discussions, careful revision, and final review and finalization by relevant departments.
This specification is divided into 7 chapters, 13 sections and 6 appendices. The contents of this comprehensive revision mainly include:
⑴ Added a chapter on “Terms and Symbols”; ⑵ Added a “water-type fire extinguisher for extinguishing Class B fires”, which changed the situation of water-type fire extinguishers in China that could only extinguish Type A fires and could not extinguish Type B fires; ⑶ Fire extinguishers The height of the bottom from the ground should not be less than 0.15m and adjusted to 0.08m; ⑷ For the fire extinguisher setting points with visual obstacles, a light-emitting sign indicating its location should be set; 类 A fire extinguisher configuration benchmark; 类 B fire extinguisher configuration benchmark; Reduction coefficient of fire extinguishers; 程序 Calculation procedures for the design of building fire extinguisher configuration; 修改 Modify the "effectiveness of fire extinguishing" to "fire extinguishing effectiveness and generality of fire extinguishers" as one of the factors to be considered when selecting fire extinguishers; ⑽ When there are different General fire extinguishers should be used when there is a type of fire; ⑾ delete the administrative provisions on the halogenated fire extinguishers; ⑿ add the provisions that "the location and number of fire extinguisher installation points should be determined according to the maximum protection distance of the fire extinguishers", etc.
If a partial revision of this code is required, the information and provisions of the partial revision will be published in the "Engineering Construction Standardization" magazine.
The provisions in this code marked with bold type are mandatory and must be strictly implemented.
The Ministry of Construction is responsible for the management and interpretation of the compulsory provisions, the Fire Bureau of the Ministry of Public Security is responsible for the daily management, and the Shanghai Fire Research Institute of the Ministry of Public Security is responsible for the specific content interpretation. During the implementation of this code, all units are required to combine engineering practices and carefully summarize their experience. If any changes or additions are found, please send comments and suggestions to the management group of "Code for Design of Building Fire Extinguisher Configuration" of the Shanghai Fire Research Institute of the Ministry of Public Security ( Address: No. 601, Zhongshan South Second Road, Shanghai, 200032, Fax: 021-54961900) for future modification and addition.
The main editing unit, participating editing unit and main drafter of this code:
Compiling institutes : Shanghai Fire Research Institute of Ministry of Public Security
Participating organization: Fire Bureau of Tibet Autonomous Region
China Coal International Engineering Group Beijing Huayu Engineering Co., Ltd.
Handan City Public Security Fire Station
Shenzhen Public Security Fire Bureau
Chinese People's Armed Police Force Academy
Qingdao Public Security Fire Bureau
Chongqing Fire Bureau
Beijing Fire Research Institute
Dalian Public Security Fire Bureau
Nanjing Banqiao Fire Fighting Equipment Factory
Anhui Huaxing Wuhu Iron Fan Fire Fighting Group
The main drafters: Hu Chuanping, Tang Zhuhua, Liu Baoping, Zhu Rong, Nan Jianglin, Zhang Zhili, Guo Xiuyan, Chen Qingdi, Zhang Xuekui, Zhao Rui, Liu Kang, Gao Xiaobin, Yi Yongsheng, Wang Baowei, Zhao Lunyuan, Zheng Yu